PLANNING BOARD CERTIFICATE OF ACTION
SITE PLAN
Re: MMED Utility Storage Garage High Street/West Church Street
Engineer: TBA Architects, Inc.
Owner: Mansfield Municipal Electric Department
Dear Ms. Staples:
Please be advised that on Wednesday, January 27, 2021, the Mansfield Planning Board conducted
a public meeting and discussed the above -referenced site plan for the Mansfield Municipal
Electric Department at High Street/West Church Street in accordance with Mansfield Zoning By -
Law Section 230-5.3, Site Plan.
At that meeting, the Mansfield Planning Board, with six (6) members present, voted to approve
the site plan application titled "MMED Storage Building W. Church St. Mansfield, MA" dated
November 13, 2020 and prepared by TBA Architects, Inc:
The following documents were introduced at the public meeting:
a. Copy of the site plan application, filed with the Town Clerk's office November 16, 2020;
b. Plan titled "MMED Storage Building W. Church St. Mansfield, MA" dated November
13, 2020 and prepared by TBA Architects, Inc.;
c. November 17, 2020 memo from Shaun P. Burke, Director of Planning and Development;
d. January 20, 2021 memo from Joshua Reinke, EIT and Rick Alves, PE, Engineering
Department;
e. Sheet I of 1 of photometric plan "Mansfield Municipal Storage Building" dated January 27,
2021.
Motion: On January 27, 2021, the Mansfield Planning Board, with six (6) members present,
voted six (6) in favor with zero (0) opposed and zero (0) abstentions to approve the site plan
application for the MMED Storage Building as shown on the plan titled "MMED Storage
Building W. Church St. Mansfield, MA" dated November 13, 2020 and prepared by TBA
Architects, Inc. with the following conditions:
1. Any and all department head comments (attached) must be completely addressed prior
to the issuance of a building permit(s);
i,
2. Hours of operation for demolition, construction deliveries, site work and construction shall be
MMED Storage Garage
Page 2 of 2
limited to 7:00 a.m. to 5:00 p.m. Monday through Friday and 8:00 a.m. to 4:00 p.m. on Saturday.
No work shall be done on Sunday. These restricted homy ofoperation shall not apply to interior
work. All loaded vehicles shall be suitably covered'to prevent dust and contents leaving the
vehicle and to protect abutters and other residents, and the public way from material spilled from
the load. All public rights -of -way shall be maintained free of all mud, stones or any other
conditions that may result in a public safety hazard for vehicles or pedestrians. Sweeping or
cleaning must be completed daily or more frequently as deemed necessary during the operation,
as directed by the Mansfield Police Chief. The applicant may be required to have a police officer
present during any hauling on or off site. The applicant shall consult with the Mansfield Police
Chief as to whether or not this may be necessary and to discuss the best hauling routes. Erosion
control measures should be installed around catch basins within the public right-of-way.
(Penney-Cerretani)
Friedman — In favor
LeCesne — In favor
Penney — In favor
McClanahan — In favor
Ashman -Collins — In favor
Cerretani — In favor
Six (6) in favor. Zero (0) opposed. Zero (0) abstained. PASSES
Therefore, by a vote of six (6) in favor with zero (0) opposed and zero (0) abstentions, the site
plan application for the "MMED Storage Building W.'Church Si Mansfield, MA" dated
November 13, 2020 and prepared by TBA Architects,, Inc. is hereby approved.
If you have any questions, please contact the Planning Department.
Sincerely, / It �J
r�`e << 141 /� C, (C C 44 /
Beth Ashman -Collins, Chair
Mansfield Planning Board
Attachments
Cc: Joseph Sollectio, Manager, Mansfield Municipal Electric Department
Robert J. Blackman, Inspector of,Buil,dings/Zoning EnforcementOfficer
Richard Alves, Jr., P.E., Town ,,EngineWAssistantDPW Director
BAC/jd
Town of Mansfield
6 Park Row, Manoeld, Masracbmeas 02048
D, artment of Public Forks
Town. Engineer/Assistant DPW Director
Richard C. Alves, Jr., PE
MEMORANDUM
TO: Shaun Burke, AICP, Director of Planning & Community Development
FROM: Joshua W. Reinke EIT, Engineer II/3WR
Richard C. Alves, Jr. PE, Town Engineer/Assistant DPW Director/ -CA
DATE: January 20, 2021
SUBJECT: Site Plan Application, 125 High Street, Proposed MMED Storage Garage
Note: Site Plans and Drainage Calculations submitted by Samiotes Consultants, Inc. dtd. 11113120,
The Engineering Division provides the following comments, recommendations & questions:
1. Please highlight the top of bankand'base flood`elevaiion lines on the plan set.
2. Please indicate the location of accessible parking within the parking lot.
3. Drain pipes should match crowns.
4. We recommend the 8" PVC drain pipe that runs 62 feet be changed to Ductile Iron Pipe
due to lack of minimal cover over the pipe. The 8" DI is permissible due to the outlet
pipe being of the same diameter.
5. We recommend against using a trench drain as, in our experience; they frequently clog
and cease to function properly.
6. The Town requires mulch socks be used in lieu of straw wattles.
Questions:
1. Is sewer service being brought to the building? If so, please indicate on the plan set.
2. Does the 6" PVC pipe running under the slab meet Plumbing Code?.
3. Is there any increase in disturbance within the Riparian Zone?
Cc: Robert Blackman, Inspector of Buildings & Zoning Enforcement Officer
Katelyn Merrill, Environmental & Conservation Planner
Phone (508)261-7377 . • Fax (508)261-7425 Emailralves@mansfteldma.com
Town of Mansfield
6 Park Row, Mansfield, Massachusetts 02048
Planning Department
Shaun P. Burke
Director of Planning and Development
I1T/i_�i\ ["1, \ll��_ 1"jiI
TO: Robert J. Blackman, Inspector of Buildings/Zoning Enforcement Officer
FROM: Shaun P. Burke, Director of Planning and Development
DATE: November 17, 2020
SUBJECT: Site Plan Application — MMED Storage Garage - High Street/West Church Street
I have reviewed the above -referenced site for conformity to local by-laws, in the
Mansfield Zoning By -Law and sound planning practices, and offer the following:
1. The proposed municipal use is allowed in the underlying zone, Industrial 3 (I3).
2. The proposed building meets both the required setbacks and FAR for the underlying
zone.
3. The building as shown appears to be storage only. If there will be office space or other
similar uses proposed, they should be shown on the plans.
4. The site is, for the most part, within the 200-foot outer riparian zone.
5. Approximately one -quarter of the site is within the 100-foot inner riparian zone. The
proposed building appears to be wholly within the 100-foot inner riparian zone.
6. The proposed building abuts or lies within the 100-year floodplain zone, the "AE Zone."
7. The rear of the proposed building abuts the 25-foot Conservation Commission No -Touch
Zone.
8. The applicant should consider relocating the proposed building to the opposite, or west,
side of the site (a mirror image to the current proposal). By relocating the proposed
building, the issues raised in items 4, 5, 6 and 7 above would be addressed.
Phone (508)261-7363 Fax (508)261-7343 Emailsburke@mansfieldma.com
9. With a minor image of the proposed building, the rear of the proposed building would be
accessible by the Mansfield Fire Department from West Church Street, although there is
a chain link fence at that location from the public way.
10. Is the site subject to an Activity Use Limitation (AUL)? I am concerned about excavation
for the proposed rain garden.
11. Is there a fire hydrant located on site? If not, there should be at least one located within
the fenced area.
12, Will there be any lighting on the building itself? Is so, lighting should be shown.
Municipal Clearinghouse
The Planning Board, under the Town's Home Rule Charter, must make a recommendation to the
Select Board on all municipal projects. Based on the proposal and the site suitability, I think
Planning Board support should be offered to the Select Board on this project. While the building
could be relocated on the parcel, the need for the equipment building is clear and the proposed
use is the same or similar to the existing use. The parcel, located in the I3 zone and subject to an
AUL, will be substantially improved by the site work, stormwater management improvements
and indoor storage of trucks and materials.
If you have any questions or would like to discuss any of the above in further detail, please feel
free to contact me.